K+G Control Unit RWZ
The K+G Control Unit RWZ is a family of Smoke and Heat Exhaust Ventilation System (SHEVS) control centres for 24 V actuators. These control panels are designed for smoke extraction and natural ventilation applications in buildings that require supervised fire signal lines, emergency battery backup, monitored actuator circuits and reliable alarm-driven opening logic. The RWZ product range includes compact single-group control units as well as higher-capacity multi-output versions for more advanced smoke ventilation projects.
Table Of Contents
- Concept Of Electric Control Centres
- Standard Features Of RWZ SHEVS Control Centres
- RWZ 1b, RWZ 4d And RWZ 5e Versions
- Options And Accessories
- Technical Documentation And Downloads
Concept Of Electric Control Centres
The RWZ product family is based on the concept of electric SHEVS control centres designed for the operation of smoke and heat exhaust systems with 24 V actuators. In practical building use, these control centres act as the decision-making and power-supply layer between detectors, manual fire buttons, weather systems and the actuator groups responsible for opening smoke vents or ventilation windows.
This type of control centre is used where the smoke exhaust strategy depends on electrically driven opening devices and where the installation must continue to function safely during power failure. For that reason, the RWZ range combines power supply, line supervision, fire input logic, alarm indication and actuator control inside a dedicated smoke ventilation cabinet.
From an SEO perspective, these products fit exactly into searches such as SHEVS control centre, 24 V smoke ventilation control panel, smoke and heat exhaust control unit and control centre for smoke exhaust actuators.
Standard Features Of RWZ SHEVS Control Centres
The FUMARO page lists a common feature set for all RWZ control centres. These functions define the practical operating logic of the system and explain why the RWZ range is suitable for smoke exhaust applications in commercial, public and technical buildings.
- 24 V output for actuators, with direction of motion changed by reversing polarity
- Signal line for automatic fire detectors
- Signal line for fire alarm button, including non-automatic fire detectors
- Emergency power supply for at least 72 hours with automatic recharging
- Monitoring of signal lines for wire breakage and short-circuit
- Monitoring of accumulator, mains and fuse failure
- Monitoring of the actuator bus line for wire breakage
- Internal indication of Operation, Alarm and Malfunction status
- Connection of a fire alarm button with status indication and reset function
- Possibility of connecting a Fire Alarm Control Panel for alarm triggering
- Possibility of connecting a wind and rain control system
- Reverse-connect and deep-discharge protection of the batteries
- Cycle repetition for reliable opening in the case of SHE operation
- Selectable automatic closing after alarm reset
- Selectable “Malfunction = Alarm” function
- Adjustable maximum ventilation position with stroke limitation
- Manual ventilation in start-stop mode or dead-man mode
- Use of VdS-approved accumulators
In practice, this means the RWZ range is not just a simple power box for actuators. It is a fully supervised fire safety control centre intended to combine smoke exhaust, manual activation, monitored fire signal lines, weather logic and standby battery operation in one system.
RWZ 1b, RWZ 4d And RWZ 5e Versions
The FUMARO page presents three core RWZ families, each aimed at a different project scale. Together they cover everything from compact single-group installations up to larger systems with multiple outputs and higher actuator load.
| Version | Main Characteristics | Typical Types |
|---|---|---|
| RWZ 1b | SHEVS control centre for connection of 24 V actuators with one smoke and heat exhaust group, 2 signal lines and max. 4 A output current. VdS approval according to VdS 2581 and VdS 2593. Internal power supply designed and certified to DIN EN 12101-10. Control unit designed and tested to prEN 12101-9. | RWZ 1-4b, max. 4 A output current |
| RWZ 4d | SHEVS control centre for connection of 24 V actuators with one smoke and heat exhaust group, 3 signal lines and max. 8 A output current. VdS approval according to VdS 2581 and VdS 2593. Internal power supply designed and certified to DIN EN 12101-10. Control unit designed and tested to prEN 12101-9. | RWZ 4-8d, max. 8 A output current |
| RWZ 5e | SHEVS control centre with four outputs for 24 V actuators. Selectable group configuration: one or two SHE groups and up to four ventilation groups. Maximum output current up to 32 A. VdS approval to VdS 2581 and VdS 2593. Internal power supply designed and certified to DIN EN 12101-10. Control unit designed and tested to prEN 12101-9. |
RWZ 5-8e, max. 8 A RWZ 5-16e, max. 16 A RWZ 5-24e, max. 24 A RWZ 5-32e, max. 32 A |
In practical selection terms, the RWZ 1b is a compact solution for small systems, the RWZ 4d offers a higher-capacity single-group solution with additional signal handling, and the RWZ 5e extends the concept to multiple outputs and more complex group configurations. This makes the RWZ family suitable both for basic smoke exhaust systems and for larger projects where several actuator outputs and ventilation groups must be coordinated by one control centre.
Options And Accessories
The FUMARO page also specifies additional options and accessories available for selected RWZ versions. These options are important in real projects because they extend alarm forwarding, weather control and external warning functions.
| Option | Description | Applicable Versions |
|---|---|---|
| PK | One potential-free contact each for alarm and malfunction forwarding | RWZ 1, 2, 4, 5, RWD |
| PK-SA | Potential-free contacts for forwarding indication of position | RWZ 5 |
| WRM | Internal wind and rain control | RWZ 1, 4d, 5, RWD |
| WTM | Outputs for external warning devices in case of alarm or malfunction, for example sounders and strobes | RWZ 4d, 5, RWD |
These options make the RWZ system easier to integrate with external monitoring, warning logic and weather-dependent control. For designers and installers, that is particularly useful when the smoke exhaust panel has to work together with local alarm indication, fire alarm forwarding or automatic weather closing functions.
Technical Documentation And Downloads
The original FUMARO page provides a dedicated download area for the RWZ system. The available files listed there are shown below in English form.